Modbus

Implementation of Modbus protocol using Arduino over RS485 [Full-Duplex] and Ethernet (TCP/IP) and Stm32 over RS485 (Half duplex with HAL driver) .


Modbus master

Master request Packet Info :

  • It contains 8 bytes out of which last 2-bytes are CRC bytes.
  • Modbus uses Big Indian format [MSB (most significant Byte not bit) is sent first] .

Master request Packet : Slave_address | Function_Code | offset_High_Byte | offset_Low_Byte | readLength_High | readLength_Low | CRC_High | CRC_Low


Modbus Slave

Slave response Packet Info :

Size of Response of is not fixed because master can request Bytes ranging from [1-255]

Slave request Packet : Slave_address | Function_Code | No_of_ data_ bytes [not no of registers] after Slave_address byte and Function Code byte except CRC bytes|Data byte 1 | Data Byte 2 |...... | CRC_High | CRC_Low


Read this to get more info : http://www.simplymodbus.ca/FC03.htm

To read and Parse Float / long (4-Bytes)

  • Maximum size of registers in Modbus is 16-bits i.e. 2-Bytes long. It means to read a value which is split into two registers you must read two register and then combine the value.

  • To read Float or Long integers which are 4-Bytes wide values. Master must pass a request to read two register (16 bit wide each) and then combine the result of into single 32-bit register.

Converting Hex to Float ->

  • The preffered way of doining this is to make union which contains int ,char array[4] and float as members (assuming int and float are 4-bytes long [size of float and int are 4-bytes in 32 bit architecture (both PC and ARM controllers)] ). Now Copy the contents of received bytes into char array of union in little endian (Modbus slave sends the data in Big endian). Then make a variable float f and then equate it to the union float member . This will automatically give you the correct float value.
  • Alternatively- Combine the received data bytes temp into int32_t variable and Now store this int32_t combined variable into int32_t member of union . Then make a variable float f and then equate it to the union float member . This will automatically give you the correct float value.

Modbus Exception

They are generally sent by receiver when you try to access particular register which is not valid.

Exception Packet : Slave_address | Function_Code |Exception Code | CRC_High | CRC_Low

Read this to get more info about Exception : http://www.simplymodbus.ca/exceptions.htm

Useful links

https://gregstoll.dyndns.org/~gregstoll/floattohex/ https://www.lammertbies.nl/comm/info/crc-calculation.html http://projectsfromtech.blogspot.in/2013/09/combine-2-bytes-into-int-on-arduino.html https://stackoverflow.com/questions/2182002/convert-big-endian-to-little-endian-in-c-without-using-provided-func