Add schleifenbauer PDU #1217
base: main
Are you sure you want to change the base?
Add schleifenbauer PDU #1217
Conversation
Hi @Wqrld, could you please provide the updated generator/generator.yml and add the needed mib files for this to work to the Makefile? |
The generator was also failing locally before adding my patch because of 404's, i had to rip those out of the makefile to generate this configuration. |
I do not have the rights to those original mib files so i'm not sure if i'm allowed to add them. They were taken from https://docs.schleifenbauer.eu/?dir=Interfaces/SNMP |
Shouldn't be an issue to curl their public available mib files in the generator/Makefile |
Signed-off-by: Luc H <[email protected]>
Signed-off-by: Luc H <[email protected]>
$(eval TMP := $(shell mktemp)) | ||
@echo ">> Downloading schleifenbauer to $(TMP)" | ||
@curl $(CURL_OPTS) -o $(TMP) $(SCHLEIFENBAUER_URL) | ||
@unzip -j -d $(MIBDIR) $(TMP) SCHLEIFENBAUER-PRODUCTS-MIB.txt SCHLEIFENBAUER-DATABUS-MIB.txt SCHLEIFENBAUER-SMI.txt |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
The SCHLEIFENBAUER-PRODUCTS-MIB.txt seems not to be included in this zipfile, only in the older https://docs.schleifenbauer.eu/Interfaces/SNMP/PDU_mib_244.zip. If the file is necessary we'd need to get it from the 2nd zipfile.
Signed-off-by: Luc H <[email protected]>
# https://docs.schleifenbauer.eu/?dir=Interfaces/SNMP | ||
schleifenbauer: | ||
walk: | ||
- 1.3.6.1.4.1.31034.12 |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
This OID is overly broad. I think we want to be more targeted here with which walks to include. Some of the metrics included by this are read-write settings OIDs that have no meaning as metrics.
Let's start with the most useful part, the device table.
- 1.3.6.1.4.1.31034.12 | |
- sdbMgmtCtrlDevicesTable |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I think almost everything in 1.3.6.1.4.1.31034.12.1.1.2 would be of use, which is basically the whole generated list. There are a few you could leave out, but for my usecase more is better.
This patch adds support for Power Distribution Units from https://www.schleifenbauer.eu
I was able to successfully read out my PDU's into grafana. I hope this may be useful for others too.
Note:
This query takes about one minute to run on my device, running into timeouts. Adding
fixes this. I think this is an issue with many SNMP devices, so it might be an idea to add statements like these (with lower limits) to the readme example.